Wide Pressure 120VAC 60Hz ON OFF Sensor Control Motion Compact Size
Wide Pressure 120VAC 60Hz Control Motion ON OFF Sensor
Setting of ON/OFF sensor:
Detection area
In this area,movement will be detected and able to trigger the sensor.100% detection area is also
known as the strong sensitvity.
Hold-time
The period of light keeping 100% brightness after moving objects leave the detection area.
Daylight threshold
Definition of the ambient brightness; only when the ambient brightness is lower than the preset
specific lux amount, the sensor will work; when it's preset as "disable",the sensor works everytime it
detects motion regardless the ambient brightness.
Features of ON/OFF Sensor:
1. Automatic On/off control with Daylight sensor.
2. Optional detection range, holdtime and daylight threshold .
3. Compact sized particularly suitable for Ceiling lights or Bulkhead.
4. Loop in and loop out for easy installation.
5. 5 years warranty.
Detection area of ON/OFF sensor:
This figure indicates the maximum distance at the highest mounting height with 100% sensitivity.
Typical installation height 2-5m
Motion detection 0.5~1.5m/s
Mounting height 2-5m (ceiling mounted)
Detection angle ≤150°(Without glass)
Detection range Radius,3-6m (ceiling mounted)
Mechanical structure of ON/OFF sensor:
Certificate RED RoHS CE
Detection area 100%/50%
Setting mode DIP switch
Hold time 5s/60s/3min/10min
Daylight threshold 30Lux/disable
Dimensions (Unit: mm) of ON/OFF sensor:
Size L*W*H:60.6*35.5*25.1MM
Operating temperature -25°C~+60°C
Warranty 5 years
Function setting By 4 dial switvh
IP grade IP 20
Wiring diagram of ON/OFF sensor:
Control mode ON/OFF
Connection type Amphenol connector(L,N,N,L')
Switching capacity 300W(Impedance load),100W(capacitive load)
Stand-by power ≤0.5W
Microwave frequency 5.8GHz±75MHz
Microwave power <0.3mW
Operating voltage 120VAC 60Hz
Application of ON/OFF motion sensor:
1. Automatically ON/OFF function:
With sufficient daylight,even when motion detected,light remains OFF.
With insufficient daylight,when motion detected,light ON.
After the last detection,and the present hold time elapsed,light OFF.
2. No daylight function
When the daylight threshold is set to "Disable".
Light on when detect movement, After people leave, Light off after stand-by period.
Applications: Dim places such as Basement Parking, Underpass.
When motion is detected, the sensor will switch on the light to 100% brighteness.
After people leave the detection area, light remains 100% brightness within hold time.
After the last detection and the present hold time elapsed, light OFF.